Receptacle Outlets Under Counter with 6″ Overhang 210.52C

I have this scenerio often.

Receptacle Outlets under counter
Receptacle Outlets under counter

The Receptacle Outlet above now has a plate over it. In my opinion it was OK. The 2005 NEC says that

Now of course we would have to read the whole code section, but from above the outlets discussed are only the required outlets and this outlet is not required. This outlet is not required as stated in another exception.

Exception: Receptacle outlets shall not be required on a
wall directly behind a range or sink in the installation described
in Figure 210.52

I think this outlet was OK. 

Exception to (5): To comply with the conditions specified in
(1) or (2), receptacle outlets shall be permitted to be
mounted not more than 300 mm (12 in.) below the countertop.
Receptacles mounted below a countertop in accordance
with this exception shall not be located where the
countertop extends more than 150 mm (6 in.) beyond its
support base.

Filed under Electrical, Uncategorized by .

Comments on Receptacle Outlets Under Counter with 6″ Overhang 210.52C

August 24, 2009

Tony Tidwell
2:00 pm #

It depends…..Is the receptacle required to satisfy 210.52(A)(2)(3)concerning wall space?

November 12, 2009

willie fortner
12:26 pm #

This is very common;most houses has this receptacle. If it is within 6 foot of sink it must be GFCI protected